These kind of units have been studied and designed
for all those applications where a simultaneous cold water and
warm water production is required, for example: Hospitals, Hotels,
Sporting Centres, Industrial Plants and so on.
It's basically a 4-pipes heat pump with 2 independent and not
interchangeable circuits aimed to the cold and warm water production.
Each cooling circuit is therefore supplied with an additional
condenser/recovery able to produce warm water, when needed.
The unit's control system is totally automatic and is carried
out through an electronic microprocessor installed on board.
Operation Modes
Mode 1: Only Cooling Mode
When the warm water production is not required, the unit runs
as a water chiller and produces only cold water. With such a
running mode and in order to complete the cooling process, the
evaporator and the condensing coil with air-cooled fins are the
exchangers in use.
Mode 2: Cooling Mode with heat recovery
When warm water is required as well, the unit can operate as
water chiller and produce warm water at the same time, without
costs and exploiting the heating power of the condensing process.
With such a running mode and in order to complete the cooling
process the evaporator and the condenser/recovery (which is water-cooled
and where the condensing process takes place) are the exchangers
in use.
Mode 3: Heat Pump Mode
The unit runs as an heat pump and therefore produces warm water.
With such a running mode and in order to complete the cooling
process, the finned condensing coil (as evaporator) and the condenser/recovery
(which is water-cooled and where the condensing process takes
place) are the exchangers in use.
On units with more than 1 circuit, all above mentioned running
modes are possible at the same time on different circuits (i.e.
on a 2-circuits unit the circuit 1 can be in Mode 1 and the circuit
2 can be in mode 2 or 3).
More Details
Specifications are subject to change without prior notice.
|